MidSun High Voltage Insulation E/Insulation |
| |
 |
Super tough silicone split line hose for distribution lines and substations cable and bus. Virtually permanent, flame and arc resistant, and won't discolour like EPDM "instant" insulation systems.
E/INSULATION™ is a minimum 20kV phase-to-ground flame and arc resistant coverup. Electrically insulating and made from High Temperature Vulcanized Silicone, it is split for ease of application. The silicone of E/INSULATION™ is the same type commonly used for polymer or non-ceramic insulators being sold today. |
| |
|
The hose is simply pulled on and split apart allowing it to be slipped into round or angle susbstation cable or bus.
Because E/INSULATION™ is formed from High Temperature Vulcanized Silicone, it is very pliable at all temperatures, yet it is tough and robust to allow extremely rough handling, the abuse of line trucks and hundreds of on and off applications.
|
|
Specifications
|
|
|
•Colours
|
Grey, Black, Orange
|
|
|
•Hardness, Shore A
|
25-85
|
|
|
•Durometer (ASTM D2240)
|
65 + 5
|
|
|
•Tensile Strength, p.s.i. (ASTM D412)
|
600
|
|
|
•Elongation @ Break (ASTM D412)
|
400
|
|
|
•Breaking strength
|
Excellent
|
|
|
•Brittle Point, oF (ASTM D74C)
|
-90
|
|
|
•Dielectric Strength (ASTM D-149) v/mil
|
550
|
|
|
•U.V. Weathering/5000 hours (ASTM G53)
|
No significant change
|
|
|
•Chemical Resistance
|
Excellent
|
|
| •Fire Retardance (UL 94) |
Self Extinguished in 15 sec. |
|
Values listed above are typical properties and should not be used for preparation or specifications. * Tested using 40 mil test slabs. |
|
|
|
|
E/INSULATION™ is used for the purpose of:
•Preventing tree and animal contact outages on uninsulated cable •Covering and insulating substation aluminium and copper bus and cable, as well as distribution lines •Residential weather head cable covering, replacing expensive line hose
E/INSULATION™ •Can be left in place •Will not change colour over time •Will not chalk •Prevents voltage puncture from phase-to-ground or phase-to-phase contact |
|
E/INSULATION™ is used for the purpose of:
•Preventing tree and animal contact outages on uninsulated cable •Covering and insulating substation aluminium and copper bus and cable, as well as distribution lines •Residential weather head cable covering, replacing expensive line hose |
| Use E/lnsulation size that ID fits the OD of bus. Use proper shape of E/lnsulation (round, angle, T-shape or flat). Simply split silicone E/lnsulation tube and wrap around bus or conductor. On horizontal bus face slit down to prevent water from entering. For E/lnsulation over 900mm long, it is recommended that E/Fusing Tape be used to hold section in place. Midsun recommends that E/lnsulation be used to allow for a minimum 400mm to 500mm clearance for phase to phase and phase to ground contacts. |
|
|
|
|
| |
| |