The EPS2 switch can be installed either:
• Sitting on top of two cross-arms either side of a wooden / concrete pole
• Sitting on top of two tee brackets which are bolted to the concrete / wooden pole
• Sitting on top of mid pole brackets under sub-transmission
|
|
EP2 Electropar Switch 11 kV
|
|
Nominal Voltage Application
|
22kV
|
|
Maximum Applicable Voltage
|
25 kV
|
|
BIL
|
150kV
|
|
Momentary Fault Rating
|
40 kA
|
|
1 Second Fault Rating
|
25 kA
|
|
3 Second Fault Rating
|
16 kA
|
|
1 Time Duty Cycle Fault Close Rating
|
20 kA
|
|
3 Time Duty Cycle Fault Close Rating
|
15 kA
|
|
Continuous Current Rating
|
900Amps
|
|
Emergency Current Rating
|
1000Amps
|
|
Load Interrupt Rating
|
600Amps
|
|
Max Emergency Load
Interrupt
|
1000Amps
|
|
Gross Weight Complete Switch
|
87kg
|
|